safety-gate2026-08-28SR/02333/26

CILIA — Circuit breaker — Circuit-breakers for overcurrent protection

The circuit braker is not sensitive enough and can get stuck in the open position. Moreover the polyethylene plate of the device can melt. This can lead to a user coming into contact with live parts and receiving an electric shock. The product does not comply with the requirements of the Low Voltage Directive nor with the European standard EN 60898.

Published remedy: Type of economic operator taking notified measure(s): OtherCategory of measure(s): Withdrawal of the product from the marketDate of entry into force: Unknown